En el siguiente reporte se realiza un análisis exploratorio de datos aterrizado a las mediciones de vibraciones en los ventiladores de la Torre de enfriamiento asociada a flores IV.
## # A tibble: 6 × 33
## `Date Time` `4VT53107-MA` `4VT53107-RA` `4VT53107-RB` `4VT53107-RC`
## <chr> <chr> <chr> <chr> <chr>
## 1 03/27/2025 16:57:01.8… "0.00 " "0.00 " "0.00 " "0.00 "
## 2 03/27/2025 14:54:03.6… "0.00 " "0.00 " "0.00 " "0.00 "
## 3 03/27/2025 12:51:05.4… "0.00 " "0.00 " "0.00 " "0.00 "
## 4 03/27/2025 10:48:07.2… "0.00 " "0.00 " "0.00 " "0.00 "
## 5 03/27/2025 08:45:09 "0.00 " "0.00 " "0.00 " "0.00 "
## 6 03/27/2025 06:42:10.8… "0.00 " "0.00 " "0.00 " "0.00 "
## # ℹ 28 more variables: `4VT53106-MA` <chr>, `4VT53106-RA` <chr>,
## # `4VT53106-RB` <chr>, `4VT53106-RC` <chr>, `4VT53105-MA` <chr>,
## # `4VT53105-RA` <chr>, `4VT53105-RB` <chr>, `4VT53105-RC` <chr>,
## # `4VT53104-MA` <chr>, `4VT53104-RA` <chr>, `4VT53104-RB` <chr>,
## # `4VT53104-RC` <chr>, `4VT53108-MA` <chr>, `4VT53108-RA` <chr>,
## # `4VT53108-RB` <chr>, `4VT53108-RC` <chr>, `4VT53109-MA` <chr>,
## # `4VT53109-RA` <chr>, `4VT53109-RB` <chr>, `4VT53109-RC` <chr>, …
## # A tibble: 20 × 3
## DateTime SensorTag Vibration_Raw
## <chr> <chr> <chr>
## 1 03/27/2025 16:57:01.800 4VT53107-MA "0.00 "
## 2 03/27/2025 16:57:01.800 4VT53107-RA "0.00 "
## 3 03/27/2025 16:57:01.800 4VT53107-RB "0.00 "
## 4 03/27/2025 16:57:01.800 4VT53107-RC "0.00 "
## 5 03/27/2025 16:57:01.800 4VT53106-MA "0.02 "
## 6 03/27/2025 16:57:01.800 4VT53106-RA "0.02 "
## 7 03/27/2025 16:57:01.800 4VT53106-RB "0.08 "
## 8 03/27/2025 16:57:01.800 4VT53106-RC "0.02 "
## 9 03/27/2025 16:57:01.800 4VT53105-MA "0.02 "
## 10 03/27/2025 16:57:01.800 4VT53105-RA "0.00 "
## 11 03/27/2025 16:57:01.800 4VT53105-RB "0.02 "
## 12 03/27/2025 16:57:01.800 4VT53105-RC "0.03 "
## 13 03/27/2025 16:57:01.800 4VT53104-MA "0.00 "
## 14 03/27/2025 16:57:01.800 4VT53104-RA "0.00 "
## 15 03/27/2025 16:57:01.800 4VT53104-RB "0.01 "
## 16 03/27/2025 16:57:01.800 4VT53104-RC "0.02 "
## 17 03/27/2025 16:57:01.800 4VT53108-MA "0.01 "
## 18 03/27/2025 16:57:01.800 4VT53108-RA "0.01 "
## 19 03/27/2025 16:57:01.800 4VT53108-RB "0.01 "
## 20 03/27/2025 16:57:01.800 4VT53108-RC "0.02 "
## Min. 1st Qu. Median Mean 3rd Qu. Max.
## -10.080 0.010 0.770 1.325 1.470 1004.000
## Min. 1st Qu. Median
## "2024-10-08 00:00:00.00" "2024-11-19 16:14:15.45" "2025-01-01 08:28:30.90"
## Mean 3rd Qu. Max.
## "2025-01-01 08:28:30.90" "2025-02-13 00:42:46.34" "2025-03-27 16:57:01.79"
## # A tibble: 15 × 6
## DateTime Fan PointDescription SensorTag Vibration Is_Bad_Data
## <dttm> <chr> <chr> <chr> <dbl> <lgl>
## 1 2024-10-08 00:00:00 FAN 239 Motor_DE 4VT53104-… 0 TRUE
## 2 2024-10-08 02:02:58 FAN 239 Motor_DE 4VT53104-… 0 TRUE
## 3 2024-10-08 04:05:56 FAN 239 Motor_DE 4VT53104-… 0 TRUE
## 4 2024-10-08 06:08:54 FAN 239 Motor_DE 4VT53104-… 0 TRUE
## 5 2024-10-08 08:11:52 FAN 239 Motor_DE 4VT53104-… 0 TRUE
## 6 2024-10-08 10:14:51 FAN 239 Motor_DE 4VT53104-… 0 TRUE
## 7 2024-10-08 12:17:49 FAN 239 Motor_DE 4VT53104-… 0 FALSE
## 8 2024-10-08 14:20:47 FAN 239 Motor_DE 4VT53104-… 0 FALSE
## 9 2024-10-08 16:23:45 FAN 239 Motor_DE 4VT53104-… 0 TRUE
## 10 2024-10-08 18:26:43 FAN 239 Motor_DE 4VT53104-… 0 FALSE
## 11 2024-10-08 20:29:42 FAN 239 Motor_DE 4VT53104-… 0 FALSE
## 12 2024-10-08 22:32:40 FAN 239 Motor_DE 4VT53104-… 0 FALSE
## 13 2024-10-09 00:35:38 FAN 239 Motor_DE 4VT53104-… 0 FALSE
## 14 2024-10-09 02:38:36 FAN 239 Motor_DE 4VT53104-… 0 FALSE
## 15 2024-10-09 04:41:34 FAN 239 Motor_DE 4VT53104-… 0 FALSE
Para el ventilador 239 se observa errores de medición en dos puntos,
sugiriendo fallas en esos sensores (D.E. motor y el D.E. reductor)
## # A tibble: 32 × 7
## Fan PointDescription MeanVibration MedianVibration StdDevVibration
## <chr> <chr> <dbl> <dbl> <dbl>
## 1 FAN 239 Motor_DE 0 0 0
## 2 FAN 239 Reducer_DE 3.01 0 54.9
## 3 FAN 239 Reducer_IntGear 2.16 0 5.25
## 4 FAN 239 Reducer_NDE 1.28 0.58 1.35
## 5 FAN 240 Motor_DE 0.613 0.74 0.335
## 6 FAN 240 Reducer_DE 0 0 0
## 7 FAN 240 Reducer_IntGear 1.37 1.68 0.848
## 8 FAN 240 Reducer_NDE 1.38 1.75 0.835
## 9 FAN 241 Motor_DE 1.10 1.26 0.463
## 10 FAN 241 Reducer_DE 1.21 1.34 0.502
## # ℹ 22 more rows
## # ℹ 2 more variables: MaxVibration <dbl>, Count <int>