OPTIMIZING PORTABLE HIGH EFFICIENCY AIR PARTICULATE PURIFIER USE IN BRITISH COLUMBIAN LONG-TERM CARE FACILITIES

Clayton Marshall Chester1, , Ahlia Shaik1, 2, Erin Tavares1, Titus Wong2, 3, 4, Jesse Cooper1, 4


1 Vancouver Coastal Health, People Safety
2 University of British Columbia, Faculty of Medicine
3 Provincial Health Services Authority, Infection Prevention and Control
4 Vancouver Coastal Health, Personal Protection and Equipment Laboratory

Introduction

This study assessed indoor and outdoor particulate concentrations within long-term care sites with varying capacities of heating, ventilation, and air conditioning infrastructure. Staff from long-term care sites accounted for approximately half of all claims submitted by workers for COVID-19 contracted through a work-related exposure (WorkSafeBC 2023). While air purifiers can help improve indoor air quality, greater guidance is required (Canada 2023).

Objectives

  1. Evaluate HEPA purifier effectiveness with hypotheses:
  • H0: mean[PM 2.5] Control = mean[PM 2.5] Intervention
  • HA: mean[PM 2.5] Control ≠ mean[PM 2.5] Intervention
  1. From 1, develop guidance document for effective use.

Methods

Selection

Vancouver Coastal Health operates more than 120 locations across Coastal, Richmond, and Vancouver areas. Long-term care sites with varying ventilation, unit volumes, resident counts, and care intensity were selected.

(Table 1) displays gross volume of sites and units selected.

Table 1: Total gross room volume by unit and clean air delivery rate (CADR).
Site Unit Volume (\(m^{3}\)) Purifier Count Total CADR
Control 112 107.1 1 350
Long-Term Care 1 Ward 2 643.2 6 2100
Long-Term Care 2 154 92.5 1 350
Long-Term Care 2 160 133.3 1 350
Long-Term Care 2 161 100.5 1 350
Long-Term Care 3 515 155.1 1 350
Long-Term Care 3 917 33.4 1 350
a Total purifier count based on Health Canada guidance.

Sampling

Particulate matter (> 2.5 μm) concentrations were sampled using UPAS V2+ environmental samplers (Fort Collins, Colorado). Total number of purifiers selected by room volume from Health Canada guidance (2023). Outdoor concentrations of particulate matter were taken from Vancouver International Airport or North Vancouver Mahon Park. Statistical analysis completed in R Studio Version 2023.03.0.

Results

Summary statistics for all sites are shown in Table 2.

Table 2: Summary Statistics of PM 2.5 concentration (μg/m3) by Site (alphabetical).
Site Test Count Mean SD Geo. Mean Geo. SD
Control control 709 2.0 0.4 1.9 0.2
Control intervention 796 1.9 1.2 1.4 0.8
Long-Term Care 1 control 24000 3.5 3.0 2.7 0.7
Long-Term Care 1 intervention 29450 2.7 3.2 2.0 0.7
Long-Term Care 2 control 4717 0.9 0.9 0.6 0.8
Long-Term Care 2 intervention 8285 0.5 0.6 0.0 NaN
Long-Term Care 3 control 1754 3.1 1.6 2.9 0.4
Long-Term Care 3 intervention 1885 2.2 1.3 1.9 0.5

Visualization of all-site data are presented in Figure 1.

PM 2.5 reduction by site. Each box’s centre line represents median concentration. Interquartile ranges (25 and 75 percentile) reach bottom and top of boxes, respectively. Extending vertical lines (whiskers) represent minimum and maximum values. Potential outliers represented by single dots.

Figure 1: PM 2.5 reduction by site. Each box’s centre line represents median concentration. Interquartile ranges (25 and 75 percentile) reach bottom and top of boxes, respectively. Extending vertical lines (whiskers) represent minimum and maximum values. Potential outliers represented by single dots.

A time-series visualization of (log) PM 2.5 concentrations (μg/m3) is shown in Figure 2.

PM 2.5 concentration time series for November 30, 2023, at Long-Term Care 2.

Figure 2: PM 2.5 concentration time series for November 30, 2023, at Long-Term Care 2.

Discussion

Limitations

Data collection periods which included tampering (i.e., switching off devices, placing personal belongings on equipment) were removed.

Conclusion

Selected purifiers were capable of producing a meaningful PM 2.5 reduction. Some configurations (i.e., placed between staff and resident proximal to potential aerosol production) likely reduce source concentrations.

Progression

Next steps may include testing purifier effectiveness within intensive-care units and evaluating bioaerosol reduction.

Acknowledgements

We gratefully acknowledge the generous contributions from the Ministry of Health and Dawn and Axel Rehkatsch Foundation that made this work possible.