With support from the Ministry of Health, People Safety were on site at George Pearson to test the optimization of air purifiers within select rooms in the fall of 2023.
| Room | Environment | Test | Count | Mean | SD |
|---|---|---|---|---|---|
| resident | indoor | control | 5617 | 3.1 | 3.2 |
| resident | indoor | intervention | 6434 | 1.8 | 1.9 |
| staff | indoor | control | 20989 | 3.4 | 2.8 |
| staff | indoor | intervention | 22976 | 3.0 | 3.5 |
Aggregate PM 2.5 concentrations at George Pearson Centre. Six purifiers set in scattered and clustered format with PM2.5 concentration readings taken at staff and resident locations. The box’s centre line represents the median 24-hour concentration. The interquartile ranges (25 and 75 percentile) reach the bottom and top of the box, respectively. The extending vertical lines (whiskers) represent minimum and maximum values. Potential outliers are represented by single dots. Outdoor concentrations retrieved from archived PM2.5 concentration at Vancouver International Airport.
Time series for August 21, 2023. Indoor location of sample device at staff and resident sides, and six air purifiers positioned in clustered format. All six air purifiers were turned on at 1246. Outdoor concentrations retrieved from archived PM2.5 concentration at Vancouver International Airport.