Introduction

With support of Lions Gate Hospital Foundation, People Safety were on site at Evergreen House to test the optimization of air purifiers within select rooms in the fall of 2023.

Results

Summary Descriptive Statistics

Summary Statistics of PM 2.5 concentration (mg/m3) by Site (alphabetical).
Room Environment Test Count Mean SD
154 indoor control 3198 1.1 0.9
154 indoor intervention 5516 0.7 0.6
160 indoor control 1067 0.5 0.2
160 indoor intervention 1354 0.3 0.2
161 indoor control 2394 0.7 0.4
161 indoor intervention 4117 0.4 0.3
nursing indoor control 926 1.3 0.7
nursing indoor intervention 1330 1.1 0.7

Summary Visualization by Room

log PM 2.5 concentrations within Evergreen rooms 154, 160, and nursing station. One purifier within resident room. Outdoor PM 2.5 concentrations recorded from North Vancouver Mahon Park station. The box’s centre line represents the median 24-hour concentration. The interquartile ranges (25 and 75 percentile) reach the bottom and top of the box, respectively. The extending vertical lines (whiskers) represent minimum and maximum values. Potential outliers are represented by single dots.

log PM 2.5 concentrations within Evergreen rooms 154, 160, and nursing station. One purifier within resident room. Outdoor PM 2.5 concentrations recorded from North Vancouver Mahon Park station. The box’s centre line represents the median 24-hour concentration. The interquartile ranges (25 and 75 percentile) reach the bottom and top of the box, respectively. The extending vertical lines (whiskers) represent minimum and maximum values. Potential outliers are represented by single dots.

Time-Series Visualization

Time series for November 11, 2023. Indoor location of sample device within medically-enhanced care unit, and one air purifiers positioned at resident-side. Air purifier turned on at 1255. Outdoor concentrations retrieved from archived PM2.5 concentration at North Vancouver Mahon Park station.

Time series for November 11, 2023. Indoor location of sample device within medically-enhanced care unit, and one air purifiers positioned at resident-side. Air purifier turned on at 1255. Outdoor concentrations retrieved from archived PM2.5 concentration at North Vancouver Mahon Park station.

Conclusions

  • Selected purifiers were often capable of producing a meaningful reduction of PM 2.5 with most rooms
  • People Safety wish to thank Evergreen House, staff, residents, and families for their support
  • Next steps may include testing the effectiveness of bioaerosol reduction via air purifiers